Impact of Floating Neutral in Power Distribution

21/02/2015

Va propun sa cititi acest articol scris de Jignesh.Parmar dar si articolul: Intreruperea nulului in LEA jt genereaza supratensiuni

Electrical Notes & Articles

Introduction:

  • If The Neutral Conductor opens, Break or Loose at either its source side (Distribution Transformer, Generator or at Load side (Distribution Panel of Consumer), the distribution system’s neutral conductor will “float” or lose its reference ground Point. The floating neutral condition can cause voltages to float to a maximum of its Phase volts RMS relative to ground, subjecting to its unbalancing load Condition.
  •  Floating Neutral conditions in the power network have different impact depending on the type of Supply, Type of installation and Load balancing in the Distribution. Broken Neutral or Loose Neutral would damage to the connected Load or Create hazardous Touch Voltage at equipment body. Here We are trying to understand the Floating Neutral Condition in T-T distribution System.

What is Floating Neutral?

  • If the Star Point of Unbalanced Load is not joined to the Star Point of its  Power Source (Distribution Transformer or Generator) then Phase…

Vezi articolul original 2.627 de cuvinte mai mult

Intreruperea nulului in LEA jt genereaza supratensiuni

12/01/2008

SGC 2002   In imaginea alatuarata se ofera informatiile necesare intelegerii modului in care apat supratensiunile de frecventa industriala (50 hz) la intreruperea nulului in retelele electrice trifazate stradale. Aceste supratensiuni sunt in stransa legatura cu gradul de dezechilibru al impedantelor receptoarelor monofazate racordate in aval de locul in care s-a produs intreruperea nulului.

nul intrerupt 

               Cele prezentate mai sus sunt valabile si in cazul bransamentelor trifazate in cazul in care se intrerupe nulul acestora. si in acest caz se respecta regula : efectele negative se simt in aval de locul de intrerupere a nulului si sunt corelate cu gradul de dezechilibru al impedantelor receptoarelor electrice monofazate aflate sub tensiune in momentul intreruperii nulului.

              Valorile tensiunilor monofazate oscileaza mult putand fi in acelasi timp pe 1 (2) faze mai mici decat tensiunea nominala monofazata de 230V sau mai mari in domeniul periculos pentru receptoare >230 +10% , adica intre 250 V – 400 V.

               Tinand cont ca dezechilibrele dintre impedantele monofazate intr-o retea stradala se modifica continuu corelat cu conectarea / deconectarea aleatoare a receptoarelor electrice in casele (de exemplu frigiderele) si/ sau la agentii economici alimentate de reteaua stradala avariata atunci in primul rand o intrerupere de nul se recunoaste prin fluctuatii suparatoare a intensitatii luminii becurilor cu incandescenta. Desigur nu este singurul regim de functionare al retelei stradale care poate fi insotit de fluctuatii ale intensitatii luminii becurilor dar daca acest lucru este diferit fata de situatia „normala” atunci este un semnal care trebuie luat in seama. Pana la reglementarea situatiei prin eliminarea defectului ar fi de preferat ca receptoarele electrice sa fie scoase preventiv de sub tensiune.

                 Reglementarile ANRE impun ca instalatiile interioare sa fie protejate, prin grija proprietarilor/utilizatorilor acestora impotriva supratensiunilor de frecventa industriala, respectiv imotriva supratensiunilor atmosferice si de comutatie.